Air conduction and distribution in the system HVAC: cold air supply, fresh air, return air, exhaust air.
Application in the system ventilation – air conditioning – smoke extraction fire protection for high-rise buildings, commercial centers, industrial factories.
Priority is given to use when installation space is limited in height, or pipes need to be arranged close to the ceiling or along the wall.
Material
Galvanized steel Z080 (Hoa Sen / Hoa Phat) – anti-corrosion, high durability.
Standard thickness (according to pipe size and wind pressure):
0.48 mm – 0.58 mm for small size, low pressure.
0.75 mm – 0.95 mm for medium size, medium pressure.
1.15mm for large size, high pressure.
Options: Stainless steel 304/201 or powder coated steel for special environments.
Specifications – Dimensions
Cross-sectional size: W × H according to design drawings.
Standard length of each section: 1100mm for 1200mm sheet metal (optimal transportation and installation).
Shape: square or rectangular, can have rounded corners as required.
Structure & Machining
Pittsburgh seaming, lamination or gas-sealing to SMACNA/DW144.
Two end pipe attachment TDC/TDF flange or Slip & Drive for easy assembly at site.
Reinforced stiffeners along the pipe wall to prevent vibration and distortion.
The joints are sealed with airtight glue or fitted with EPDM rubber gaskets.
Application
High-rise building: shopping center, office, apartment.