{"id":4444,"date":"2025-08-05T15:28:41","date_gmt":"2025-08-05T08:28:41","guid":{"rendered":"https:\/\/onggiosaoviet.vn\/?p=4444"},"modified":"2025-08-05T15:28:41","modified_gmt":"2025-08-05T08:28:41","slug":"su-khac-nhau-giua-he-water-chiller-va-he-vrv","status":"publish","type":"post","link":"https:\/\/onggiosaoviet.vn\/en\/su-khac-nhau-giua-he-water-chiller-va-he-vrv\/","title":{"rendered":"The difference between Water Chiller system and VRV system"},"content":{"rendered":"<h2><strong>DIFFERENCES AND SIMILARITIES BETWEEN WATER CHILLER SYSTEM AND VRV SYSTEM<\/strong><\/h2>\n<p><strong>1. General description:<\/strong><\/p>\n<p>\u2013 Water Chiller system is a system that uses cold water as an intermediate coolant. Cold water is cooled in the evaporator from 12oC to 7oC and then pumped to the cooling coils for cooling. Waste heat in the condenser can be discharged into water (water-cooled chiller system) or wind (air-cooled chiller system).<\/p>\n<p>\u2013 VRV system is an air conditioning system, one condenser connected to many evaporators that we, the refrigeration engineers, call a mother with many children. Directly cooling the room with evaporators, VRV also has two types of water cooling and air cooling, but mainly air cooling.<\/p>\n<p><strong>2. Cooling capacity:<\/strong><\/p>\n<p>\u2013 The cooling capacity of the chiller system can be from several tens of KW to tens of thousands of KW. For example, the Carrier turbine compressor water-cooled centrifugal chiller, coded 17DA8-8787, has a cooling capacity of 21,000kW and a mass of 84,600kg.<\/p>\n<p>\u2013 The cooling capacity of the VRV \u2013 III 54 HP condenser is 148kW. However, a project does not limit the number of condensers, so the cooling capacity is also unlimited. Currently, there is a VRF condenser type up to 64HP with a cooling capacity of about 186kW.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/dieuhoasaoviet.vn\/upload\/images\/20621962_1925926284334026_8180588301721809561_n(1).jpg\" alt=\"\" \/><\/p>\n<p>&nbsp;<\/p>\n<p><strong>3. Application:<\/strong><\/p>\n<p>\u2013 Chiller systems are often installed to serve factories that work 3 shifts 24\/24 hours such as: fiber, printing, processing, .... In addition, they are also used for high-rise buildings and large projects with 24\/24-hour cooling needs such as: Hotels, sports complexes, hospitals ... With a floor area of over 20,000m2, cooling capacity over 3000KW. The cooling demand must be relatively stable.<\/p>\n<p>\u2013 VRV system is only used for comfort air conditioning in small, medium and large sized projects such as office buildings, hotels, hospitals, shops, supermarkets, restaurants... In particular, VRV has the feature of calculating separate electricity bills for each room, very suitable and energy-saving for local, distributed, unstable cooling applications.<\/p>\n<p><strong>4. Types of compressors:<\/strong><\/p>\n<p>\u2013 Chiller system: Many types of compressors from scroll, piston, screw to turbine<\/p>\n<p>\u2013 VRV system: mainly also spiral compressor, rotor (inverter or digital)<\/p>\n<p><strong>5. Condensing equipment:<\/strong><\/p>\n<p>\u2013 The chiller system includes a cooling condenser and a cooling tower, in addition to an air-cooled condenser.<\/p>\n<p>\u2013 With the VRV system, the condensing equipment includes an air-cooled condenser. Like the chiller system, the VRV system also has a water-cooled condenser and a cooling tower.<\/p>\n<p><strong>6. Auxiliary system:<\/strong><\/p>\n<p>\u2013 Chiller system: Includes cooling tower, cooling water pump system, expansion tank, piping system, accessories and cooling water pump<\/p>\n<p>\u2013 VRV system: None (VRV is simpler)<\/p>\n<p><strong>7. Winter heating options:<\/strong><\/p>\n<p>\u2013 Chiller system: If using a cooling tower, in winter you must use a heating resistor or use a boiler to heat water. If using an air-cooled chiller, you can use a heat pump.<\/p>\n<p>\u2013 VRV system: Heat pump is very convenient and efficient<\/p>\n<p><strong>8. Machine room:<\/strong><\/p>\n<p>\u2013 Chiller system: Need a machine room to place the chiller and pump all kinds of water.<\/p>\n<p>\u2013 VRV system: No need for machine room because the condenser can be placed on the rooftop or balcony<\/p>\n<p><strong>9. Good operation:<\/strong><\/p>\n<p>\u2013 Chiller system: Requires a team of highly skilled workers to operate, repair and maintain regularly because it is necessary to combine the Chiller with the cooling tower system, cold water pump, boiler operation...<\/p>\n<p>\u2013 VRV system: No need for operators because this system can work completely automatically, similar to a two-unit residential air conditioner.<\/p>\n<p><strong>10. Automatic capability:<\/strong><\/p>\n<p>\u2013 Chiller system: More difficult to automate because it requires a combination of three systems: chiller, cooling tower pump and cold water pump.<\/p>\n<p>\u2013 VRV system: with this system, the automatic ability is very high because there is only one refrigerant gas circulation system similar to a two-block civil air conditioner.<\/p>\n<p><strong>11. Ability to expand the air conditioning system<\/strong><\/p>\n<p>\u2013 The Chiller system cannot be expanded because the water pipe and water pump systems are fixed.<\/p>\n<p>\u2013 The VRV system has a very high expandability by installing additional units.<\/p>\n<p><strong>12. Cleaning and maintenance:<\/strong><\/p>\n<p>\u2013 With the Chiller system, maintenance is very difficult because there are many systems such as: cold, water, boiler, chemicals, cleaning equipment for condensers and cooling towers, water treatment, etc.<\/p>\n<p>\u2013 The VRV system is very simple, only needing maintenance on the condenser and evaporator units<\/p>\n<p><strong>13. Noise level:<\/strong><\/p>\n<p>\u2013 The chiller system has a higher operating noise level due to the design of the compressor and large cooling tower.<\/p>\n<p>\u2013 VRV system is lighter, compressor is designed smaller, fan capacity is small<\/p>\n<p><strong>14. Machine life and product reliability<\/strong><\/p>\n<p>\u2013 Chiller system has high life and reliability due to low speed<\/p>\n<p>\u2013 VRV system has average life and reliability due to high speed<\/p>\n<p><strong>15. Possibility of refrigerant leakage:<\/strong><\/p>\n<p>\u2013 The chiller system is not capable of leaking refrigerant.<\/p>\n<p>\u2013 VRV system has the possibility of refrigerant leakage.<\/p>\n<p><strong>16. Operating price:<\/strong><\/p>\n<p>\u2013 Chiller system: High because it requires many operators and many types of auxiliary materials.<\/p>\n<p>\u2013 VRV system: Low because most of it is fully automated<\/p>\n<p><strong>17. Power consumption:<\/strong><\/p>\n<p>\u2013 Chiller System: High<\/p>\n<p>\u2013 VRV system: Lower<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/dieuhoasaoviet.vn\/upload\/images\/z787843660897_8d9cd273cf407fae87332d815a212c21(2).jpg\" alt=\"\" \/><\/p>\n<p>If you have a need to install central air conditioning, please contact our company!<\/p>\n<p>\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014\u2014<\/p>\n<p>Contact information:<\/p>\n<p>Phone: 02253 567 618<\/p>\n<p>Hotline: Mr. Viet 0983 260 704<\/p>\n<p>Email: dieuhoasaoviet@gmail.com<\/p>\n<p>facebook: https:\/\/www.facebook.com\/dieuhoasaoviet68\/notifications\/<\/p>","protected":false},"excerpt":{"rendered":"<p>DIFFERENCES AND SIMILARITIES BETWEEN WATER CHILLER AND VRV SYSTEMS 1. General Description: \u2013 A Water Chiller system uses chilled water as an intermediate refrigerant. The chilled water is cooled in the evaporator from 12\u00b0C down to 7\u00b0C and then pumped to the cooling coils [\u2026]<\/p>","protected":false},"author":1,"featured_media":4449,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[1],"tags":[],"class_list":["post-4444","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-tin-tuc"],"_links":{"self":[{"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/posts\/4444","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/comments?post=4444"}],"version-history":[{"count":1,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/posts\/4444\/revisions"}],"predecessor-version":[{"id":4450,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/posts\/4444\/revisions\/4450"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/media\/4449"}],"wp:attachment":[{"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/media?parent=4444"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/categories?post=4444"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/onggiosaoviet.vn\/en\/wp-json\/wp\/v2\/tags?post=4444"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}